Heat transfer
WL
FOR THE REHEATING OF AIRFLOWS IN CIRCULAR DUCTING
Circular hot water heat exchanger for the reheating of airflows, suitable for VAV terminal units TVR and mechanical self-powered CAV controllers RN or VFC
- For hot water up to 100 °C
- Copper tubes arranged in two rows, with aluminium fins
- Installation in horizontal or vertical ducts independent of airflow direction
- Suitable for circular ducts to EN 1506 or EN 13180
- With lip seal and inspection access
- Maximum water-side operating pressure is 8 bar
- Casing air leakage to EN 15727, class C
EL
FOR THE ELECTRIC REHEATING OF AIRFLOWS IN CIRCULAR DUCTING
Circular electric air heater for reheating airflows, suitable for VAV terminal units TVR and mechanical self-powered CAV controllers RN and VFC
- Outlet airflow temperature 50 °C max.
- Plain heating coil, stainless steel 1.4301
- Integral overheating protection with temperature monitor (auto reset) and thermal cut-out (manual reset)
- For horizontal or vertical ducts
- Suitable for circular ducts to EN 1506 or EN 13180
- With lip seal
- Protection level: IP 43
- Casing leakage according to EN 15727, class C