Control Unit TROX UNIVERSAL

TROX UNIVERSAL

TROX UNIVERSAL CONTROLLERS FOR THE MOST DEMANDING CONTROL ENGINEERING TASKS

Electronic controller that offers plug and play communication for demanding control tasks, yet simple wiring and commissioning

 

 

  • Maximum control comfort for clean rooms, hospital wards, and offices

  • Demand-based control of supply air, extract air, room pressure and duct pressure

  • Interactive configuration software with commissioning wizard, functional testing procedure and Bluetooth adapter

  • Perfect system for complete room solutions from a single source
  • Plug-in communication cable for easy wiring
  • Adaptable control panel and many special functions allow for individual operating modes and control strategies

 

 

Expansion options

 

  • Expansion modules with LonWorks, BACnet or Modbus standard interfaces to the central BMS

  • Automatic zero point correction for long-term stability and reduced maintenance

  • Connection to the mains (230 V)
  • Adaptable control panel

 

EM-TRF

FOR THE CONNECTION OF EASYLAB TO THE 230 V MAINS

Expansion module for the direct connection of EASYLAB controllers Type TCU3 and adapter modules Type TAM to the 230 V mains

  • Double-stack terminal blocks for 230 V supply voltage connection
  • Electric plug connection to the main PCB
  • The expansion module is fitted into the casing with the EASYLAB base component

EM-TRF-USV

FOR THE CONNECTION OF EASYLAB TO THE 230 V MAINS AND FOR UNINTERRUPTIBLE POWER SUPPLY

Expansion module for the direct connection of EASYLAB controllers Type TCU3 and adapter modules Type TAM to the 230 V mains, including uninterruptible power supply

  • Double-stack terminal blocks for 230 V supply voltage connection
  • Electric plug connection to the main PCB
  • The expansion module is fitted into the casing with the EASYLAB base component
  • Uninterruptible power supply for the connected modules
  • Integral battery charging electronics with charge status indicator
  • Power failure is signalled to the EASYLAB control panels
  • Controller action in case of a power failure can be defined

EM-BAC-MOD

BACNET AND MODBUS INTERFACE FOR EASYLAB CONTROLLERS AND ADAPTER MODULES

Expansion module for EASYLAB fume cupboard controllers, room controllers, extract air controllers, supply air controllers, and adapter modules, for the integration of rooms or individual volume flow controllers with the central BMS

  • Switching between BACnet MS/TP and Modbus RTU
  • BACnet Standardised Device Profile (Annex L)
  • Modbus interface with individual data registers
  • Native BACnet interface by integrating the expansion module with EASYLAB components
  • Easy retrofitting
  • Double-stack terminal blocks for the EIA-485 bus
  • Equipment address and data transfer parameters can be defined

Interface to central BMS

  • When used on a controller with active room management function (RMF) the module provides also data points for the entire room, e.g. for total volume flows or consolidated alarms
  • When used on a single controller: data points for volume flow rate, alarm, damper blade position, or others
  • Centralised operating mode default setting, e.g. night-time operation

EM-IP

BACNET/IP INTERFACE, MODBUS/IP INTERFACE, AND WEBSERVER FOR EASYLAB CONTROLLERS AND TAM ADAPTER MODULES

Expansion module for EASYLAB fume cupboard controllers, room controllers and TAM adapter modules, for the integration of rooms or individual volume flow controllers with the central BMS, and for accessing the above mentioned devices using the integral webserver.

  • Change between BACnet/IP and Modbus/IP using the integral webserver
  • BACnet Application Specific Controller (B-ASC) according to Annex L
  • Trend logging, alarming and scheduling for selected data points
  • BACnet/IP (Annex J based on IPv4)
  • BACnet/IP interface by integrating the expansion module with EASYLAB components
  • Modbus interface with individual data registers
  • Modbus/IP (according to IEC 61158)
  • Easy retrofitting
  • Two RJ45 10/100 Mbit Ethernet connections (daisy chain is possible)
  • Multi functional Reset push button
  • Power and status indicator lights
  • MicroSD card as persistent data store for firmware, trend logging, alarming, scheduling and help files
  • Real time clock expansion module (RTC) (optional)

EM-AUTOZERO

AUTOMATIC ZERO POINT CORRECTION FOR EASYLAB

Expansion module for EASYLAB controllers that offers automatic zero point correction for long-term stable volume flow rate measurement and reduced maintenance

  • Particularly recommended for the volume flow or differential pressure measurement in sensitive areas
  • EASYLAB controller automatically identifies and uses the expansion module
  • The expansion module is fitted into the casing with the EASYLAB base component
  • Easy retrofitting
  • No additional configuration effort

BE-LCD

FOR EASYLAB FUME CUPBOARD CONTROLLERS OR ROOM CONTROLLERS, WITH TEXT DISPLAY

Control panels to be used with fume cupboard controllers or room controllers, for displaying operating values, activating functions and signalling operating states

  • Signalling of safety-related functions for fume cupboards according to EN 14175 or of operating states for rooms
  • Display of actual values, setpoint values and status messages
  • Wireless communication with Bluetooth module
  • 40-character text display
  • Push buttons for the operating mode default setting and for specific functions
  • Project-specific range of functions with configurable push buttons
  • Integral service socket for configuration and diagnosis
  • Casing suitable for flush mounting to fume cupboard side frame, or for surface mounting on a wall